Overview: The AT-08 is a high-energy ignition transformer known for its reliable ignition. It is suitable for integrated burners, radiant tube burners, high-speed burners, and industrial furnaces, capable of igniting gases such as natural gas, coke oven gas, and blast furnace gas. The AT-08 features high ignition energy, longer ignition times, and stable, reliable performance. The AT-08 offers the following advantages:
● The entire product is designed with a modular structure, making installation and wiring very convenient.
● High reliability, with minimal environmental impact.
● Instantaneous short circuits during ignition will not cause damage.
● It is compatible with the AFS258
Installation Precautions
● The AT-08 should not be installed in the following environments:
a. Areas with special chemicals or corrosive gases (such as ammonia, sulfur, chlorine, ethylene, and acidic gases).
b. Water, damp air (temperature not exceeding 90%), or condensation.
c. Places with high temperatures and frequent vibrations.
● The operating temperature of the ignition transformer should be between-20°C and +60°C. Do not operate it for extended periods at excessively high temperatures, as this can reduce its lifespan.
● Generally, the ignition transformer should be installed near the ignition burner. If the temperature near the ignition burner exceeds 60℃, install it further away from the burner.
● The yellow-green dual-color wire of the ignition transformer must be securely connected to the burner's casing and properly grounded.
● Ensure that the high-voltage output interface of the ignition transformer is tightly secured to prevent damage due to poor contact.
● To avoid interfering with other equipment, do not run the high-voltage output line of the ignition transformer through the same conduit as the signal lines of other devices; instead, use separate conduits for the wiring, and the length of the high-voltage line should not exceed 5 meters.
● Ensure that the ignition transformer's high-voltage output circuit is not short-circuited, as prolonged short-circuiting can cause permanent damage to the ignition transformer.
Technical parameters | |
Input: | AC220V 50Hz 0.5A |
Output: | ≥8KV 20mA |
Maximum power consumption: | 36W |
Ignition distance: | 3~5mm |
Ignition efficiency: | 100%ED |
Wiring form: | Three-or four-wire system |
Operating ambient temperature: | -20~+60°C |
External dimensions: | 100*92*73mm |