■ Functions and features
● Not sensitive to sunlight, infrared and light.
● There is protection against interference and short circuit in the flame signal line.
● Wide range of environmental temperature adaptation, -40~+80 C.
● It is used for flame detection of various atmospheric burners and flame retardant wind burners.
● Can be used in conjunction with burner controller.
● The maximum distance between the AVS8 flame detector and the burner controller is 50 meters (in the absence of interference).
●AVS8 comes with an insulating glass connector, fully sealed overall design, dustproof and moisture-proof.
●AVS8 is equipped with a plug-in 4-core cable, which is very easy to load and unload.
■ Installation precautions
AVS8 cannot be installed in the following environments:
a. Places where special chemicals and corrosive gases (ammonia, sulfur, chlorine, ethylene, acidic gases, etc.) exist.
b. In water, damp (humidity not exceeding 90%) or condensation.
C. Places with high temperature and frequent vibration.
The wiring of the controller connected to the probe must distinguish between the neutral and live lines, and the controller is required to be well grounded.
The flame detection line is up to 50 meters long (in the absence of interference).
Product Parameter | |
Power supply voltage: | 220-230VAC 50HZ |
Spectral range: | 190-270nm |
Maximum sensitivity: | 210+10nm |
Sensory service life: | 10000Hrs |
Detection distance: | <1.2m |
Operating ambient temperature: | -40~ +80 C |
Cabling: | four-wire, 1m long |
Gas Solenoid valve
Wind/Air Actuator valve
Manual gas and wind valve
Gas air propotional Valve
Gas regulator pressure valve
Flame detection and burner ignition controllers
Blowers
Accessories